View Offers to Buy: Equipment - Electrical - Transformers
 
61--transformers (OB1986591) (2008-02-21)

This is a combined synopsis / solicitation for commercial items prepared in
accordance with the format in far Subpart 12.6, as supplemented with
additional information included in this notice. This procurement is not a
small business set-aside; any responsible source may submit an offer. This
announcement constitutes the only solicitation; proposals are being requested
and a separate written solicitation will not be issued. Solicitation number
M67400-08-t-0092 applies and is issued as a Request for Quotation. This
solicitation document and incorporated provisions and clauses are those in
effect through Federal Acquisition Circular 2005-13 and Defense Acquisition
Circular 91-13. The naics code is 423610. The agency need is for: item no
supplies/services quantity unit unit price 0001
1 Each transformer ffp pad-mounted;
three-phase, nema C57.12.26 and as specified herein, liquid insulated (no
pcb's by jegs requirements, see 6 below), 45 kVA, 13,800 v delta pri. (95 kV
bil), dead front, radial feed, 208 y/120 v sec. 1. Compartments: a. The high
and low-voltage compartments shall be separated by steel isolating barriers
extending the full height and depth of the compartments. B. Compartment
doors: hinged lift-off type with stop in open position and three-point
latching. 2. High voltage: a. 15 kV-200 a bushing wells. B. 15 kV-200 a
loadbreak inserts (ieee std. 386). C. 15 kV-200 a oil-immersed loadbreak
switch. D. Bayonet type, oil-immersed, expulsion fuses in series with oil-
immersed, partial-range, current-limiting fuses. Coordinate transformer
protection with expulsion fuse clearing low-current faults and current-
limiting fuse clearing high-current faults beyond the interrupting rating of
the expulsion fuse. E. Parking stands. F. Ground pad. 3. Low voltage: a.
Bushings with nema 4-hole spade terminals. B. Accessories: drain valve with
sampler, fill plug, pressure relief device, liquid level gauge, pressure
vacuum gauge and dial type thermometer with maximum temperature indicator. C.
Ground pad. 4. Transformer: a. Liquid insulated, 60 Hz, 65 degrees c rise,
self-cooled type. B. Tap changer shall be externally operated, with four 2.5
percent full capacity taps, two above and two below rated primary voltage. C.
Audible sound level shall be 51 decibels or less. D. Transformer shall
include lifting lugs and provisions for jacking under base. The transformer
base construction shall be suitable for using rollers or skidding in any
direction. Provide transformer top with an access handhole. The transformer
shall have an insulated low-voltage neutral bushing with nema 4-hole spade
terminal, and with removable ground strap. 5. The insulating liquid shall be
less flammable per nfpa 70 and fm P7825, having a fire point not less than 300
degrees c per astm d 92 and dielectric strength not less than 33 kV per astm d
877. The fluid shall be a biodegradable insulating and cooling liquid, ul
classified and fm approved as "less-flammable" fluid, meeting the following
properties: a. Pour point: astm d 97, less than minus 15 degrees c. B.
Aquatic biodegradation: epa 712-c-98-075, 100%. C. Trout toxicity: oecd test
203, zero mortality of epa 600/4-90/027F, pass. 6. Pcb content: the
manufacturer must certify that the transformer does not contain any pcb's.
There is to be no detectable level of pcb's at a detection limit of less than
0.1 (zero point one) ppm. This limit is a jegs (japan environmental governing
standards) requirement that applies to marine corps bases japan. An acceptable
standard test method is astm D4059. 7. Nameplate: ieee C57.12.00 and with "pcb
content data (less than 0.1 ppm)" and "manufacturer's name and type of fluid".
8. Paint base, cabinet and tank munsell 7GY3.29/1.5 green. The paint coating
system shall comply with nema C57.12.29. 9. Routine and other tests (ieee
C57.12.00): cold resistance measurements, phase relation, ratio, no-load
losses and excitation current, load losses and impedance voltage, dielectric
(impulse, applied voltage and induced voltage) and leak. The following is to
be provided along with the offer: 1. Pcb content certification. 2. Outline
drawing of the transformer with devices indicated. 3. Nameplate data. Item no
supplies/services quantity unit unit price 0002
1 Each transformer ffp transformer,
pad-mounted; three-phase, nema C57.12.26 and as specified herein, liquid
insulated (no pcb's by jegs requirements, see 6 below), 500 kVA, 13,800 v
delta pri. (95 kV bil), dead front, radial feed, 208 y/120 v sec. See the long
description. Long description: 1. Compartments: a. The high and low-voltage
compartments shall be separated by steel isolating barriers extending the full
height and depth of the compartments. B. Compartment doors: hinged lift-off
type with stop in open position and three-point latching. 2. High voltage: a.
15 kV-200 a bushing wells. B. 15 kV-200 a loadbreak inserts (ieee std. 386).
C. 15 kV-200 a oil-immersed loadbreak switch. D. Bayonet type, oil-immersed,
expulsion fuses in series with oil-immersed, partial-range, current-limiting
fuses. Coordinate transformer protection with expulsion fuse clearing low-
current faults and current-limiting fuse clearing high-current faults beyond
the interrupting rating of the expulsion fuse. E. Parking stands. F. Ground
pad. 3. Low voltage: a. Bushings with nema 10-hole spade terminals. B.
Accessories: drain valve with sampler, fill plug, pressure relief device,
liquid level gauge, pressure vacuum gauge and dial type thermometer with
maximum temperature indicator. C. Ground pad. 4. Transformer: a. Liquid
insulated, 60 Hz, 65 degrees c rise, self-cooled type. B. Tap changer shall
be externally operated, with four 2.5 percent full capacity taps, two above
and two below rated primary voltage. C. Audible sound level shall be 56
decibels or less. D. Transformer shall include lifting lugs and provisions
for jacking under base. The transformer base construction shall be suitable
for using rollers or skidding in any direction. Provide transformer top with
an access handhole. The transformer shall have an insulated low-voltage
neutral bushing with nema 10-hole spade terminal, and with removable ground
strap. 5. The insulating liquid shall be less flammable per nfpa 70 and fm
P7825, having a fire point not less than 300 degrees c per astm d 92 and
dielectric strength not less than 33 kV per astm d 877. The fluid shall be a
biodegradable insulating and cooling liquid, ul classified and fm approved
as "less-flammable" fluid, meeting the following properties: a. Pour point:
astm d 97, less than minus 15 degrees c. B. Aquatic biodegradation: epa 712-c-
98-075, 100%. C. Trout toxicity: oecd test 203, zero mortality of epa 600/4-
90/027F, pass. 6. Pcb content: the manufacturer must certify that the
transformer does not contain any pcb's. There is to be no detectable level of
pcb's at a detection limit of less than 0.1 (zero point one) ppm. This limit
is a jegs (japan environmental governing standards) requirement that applies
to marine corps bases japan. An acceptable standard test method is astm D4059.
7. Nameplate: ieee C57.12.00 and with "pcb content data (less than 0.1 ppm)"
and "manufacturer's name and type of fluid". 8. Paint base, cabinet and tank
munsell 7GY3.29/1.5 green. The paint coating system shall comply with nema
C57.12.29. 9. Routine and other tests (ieee C57.12.00): cold resistance
measurements, phase relation, ratio, no-load losses and excitation current,
load losses and impedance voltage, dielectric (impulse, applied voltage and
induced voltage) and leak. The following is to be provided along with the
offer: 1. Pcb content certification. 2. Outline drawing of the transformer
with devices indicated. 3. Nameplate data. Item no supplies/services
quantity unit unit price 0003 1,000 Feet
cable ffp cable, power, electrical; 15 kv, type "mv-105", ul
listed, # 2, single copper conductor, 220 mil epr insulation (133% insulation
level), extruded conductor shield, extruded insulation shield, copper tape
insulation shield. See the long description. Long description: pvc jacket,
identification on the jacket, # 2 awg size. Southwire CT1-13ET or equal.cable,
power, electrical; 15 kv, type "mv-105", ul listed, # 2, single copper
conductor, 220 mil epr insulation (133% insulation level), extruded conductor
shield, extruded insulation shield, copper tape insulation shield. Item no
supplies/services quantity unit unit price 0004
6 Kit connector elbow ffp
connector, elbow, 200 amp loadbreak , 15KV 1/0 cable item no
supplies/services quantity unit unit price 0005
15 Each terminal lug ffp terminal,
lug; tap, bolted, bronze, sstl. Hardware, up to two cables (two eyebolts) to
3/4" thk flat copper pad, # 1/0 sol.-500 mcm cable size. Item no
supplies/services quantity unit unit price 0006
9 Kit connector elbow ffp connector,
loadbreak elbow kit; 200 a - 15 kV class, w/ test point, individually
packaged, 0.700 - 0.910" insul. Dia., # 1/0 awg str. Or compressed or # 2/0
awg compact conductor. Item no supplies/services quantity unit unit
price 0007 2 Each transformer
ffp transformer, pad-mounted; three-phase, nema C57.12.26 and as specified
herein, liquid insulated (no pcb's by jegs requirements, see 6 below), 112.5
kVA, 13,800 v delta pri. (95 kV bil), dead front, radial feed, 208 y/120 v
sec. See the long description. Long description: 1. Compartments: a. The high
and low-voltage compartments shall be separated by steel isolating barriers
extending the full height and depth of the compartments. B. Compartment
doors: hinged lift-off type with stop in open position and three-point
latching. 2. High voltage: a. 15 kV-200 a bushing wells. B. 15 kV-200 a
loadbreak inserts (ieee std. 386). C. 15 kV-200 a oil-immersed loadbreak
switch. D. Bayonet type, oil-immersed, expulsion fuses in series with oil-
immersed, partial-range, current-limiting fuses. Coordinate transformer
protection with expulsion fuse clearing low-current faults and current-
limiting fuse clearing high-current faults beyond the interrupting rating of
the expulsion fuse. E. Parking stands. F. Ground pad. 3. Low voltage: a.
Bushings with nema 4-hole spade terminals. B. Accessories: drain valve with
sampler, fill plug, pressure relief device, liquid level gauge, pressure
vacuum gauge and dial type thermometer with maximum temperature indicator. C.
Ground pad. 4. Transformer: a. Liquid insulated, 60 Hz, 65 degrees c rise,
self-cooled type. B. Tap changer shall be externally operated, with four 2.5
percent full capacity taps, two above and two below rated primary voltage. C.
Audible sound level shall be 55 decibels or less. D. Transformer shall
include lifting lugs and provisions for jacking under base. The transformer
base construction shall be suitable for using rollers or skidding in any
direction. Provide transformer top with an access handhole. The transformer
shall have an insulated low-voltage neutral bushing with nema 4-hole spade
terminal, and with removable ground strap. 5. The insulating liquid shall be
less flammable per nfpa 70 and fm P7825, having a fire point not less than 300
degrees c per astm d 92 and dielectric strength not less than 33 kV per astm d
877. The fluid shall be a biodegradable insulating and cooling liquid, ul
classified and fm approved as "less-flammable" fluid, meeting the following
properties: a. Pour point: astm d 97, less than minus 15 degrees c. B.
Aquatic biodegradation: epa 712-c-98-075, 100%. C. Trout toxicity: oecd test
203, zero mortality of epa 600/4-90/027F, pass. 6. Pcb content: the
manufacturer must certify that the transformer does not contain any pcb's.
There is to be no detectable level of pcb's at a detection limit of less than
0.1 (zero point one) ppm. This limit is a jegs (japan environmental governing
standards) requirement that applies to marine corps bases japan. An acceptable
standard test method is astm D4059. 7. Nameplate: ieee C57.12.00 and with "pcb
content data (less than 0.1 ppm)" and "manufacturer's name and type of fluid".
8. Paint base, cabinet and tank munsell 7GY3.29/1.5 green. The paint coating
system shall comply with nema C57.12.29. 9. Routine and other tests (ieee
C57.12.00): cold resistance measurements, phase relation, ratio, no-load
losses and excitation current, load losses and impedance voltage, dielectric
(impulse, applied voltage and induced voltage) and leak. The following is to
be provided along with the offer: 1. Pcb content certification. 2. Outline
drawing of the transformer with devices indicated. 3. Nameplate data. Item no
supplies/services quantity unit unit price 0008
1 Each transformer ffp transformer,
pad-mounted; three-phase, nema C57.12.26 and as specified herein, liquid
insulated (no pcb's by jegs requirements, see 6 below), 225 kVA, 13,800 v
delta pri. (95 kV bil), dead front, radial feed, 208 y/120 v sec. See the long
description. Long description: 1. Compartments: a. The high and low-voltage
compartments shall be separated by steel isolating barriers extending the full
height and depth of the compartments. B. Compartment doors: hinged lift-off
type with stop in open position and three-point latching. 2. High voltage: a.
15 kV-200 a bushing wells. B. 15 kV-200 a loadbreak inserts (ieee std. 386).
C. 15 kV-200 a oil-immersed loadbreak switch. D. Bayonet type, oil-immersed,
expulsion fuses in series with oil-immersed, partial-range, current-limiting
fuses. Coordinate transformer protection with expulsion fuse clearing low-
current faults and current-limiting fuse clearing high-current faults beyond
the interrupting rating of the expulsion fuse. E. Parking stands. F. Ground
pad. 3. Low voltage: a. Bushings with nema 6-hole spade terminals. B.
Accessories: drain valve with sampler, fill plug, pressure relief device,
liquid level gauge, pressure vacuum gauge and dial type thermometer with
maximum temperature indicator. C. Ground pad. 4. Transformer: a. Liquid
insulated, 60 Hz, 65 degrees c rise, self-cooled type. B. Tap changer shall
be externally operated, with four 2.5 percent full capacity taps, two above
and two below rated primary voltage. C. Audible sound level shall be 55
decibels or less. D. Transformer shall include lifting lugs and provisions
for jacking under base. The transformer base construction shall be suitable
for using rollers or skidding in any direction. Provide transformer top with
an access handhole. The transformer shall have an insulated low-voltage
neutral bushing with nema 6-hole spade terminal, and with removable ground
strap. 5. The insulating liquid shall be less flammable per nfpa 70 and fm
P7825, having a fire point not less than 300 degrees c per astm d 92 and
dielectric strength not less than 33 kV per astm d 877. The fluid shall be a
biodegradable insulating and cooling liquid, ul classified and fm approved
as "less-flammable" fluid, meeting the following properties: a. Pour point:
astm d 97, less than minus 15 degrees c. B. Aquatic biodegradation: epa 712-c-
98-075, 100%. C. Trout toxicity: oecd test 203, zero mortality of epa 600/4-
90/027F, pass. 6. Pcb content: the manufacturer must certify that the
transformer does not contain any pcb's. There is to be no detectable level of
pcb's at a detection limit of less than 0.1 (zero point one) ppm. This limit
is a jegs (japan environmental governing standards) requirement that applies
to marine corps bases japan. An acceptable standard test method is astm D4059.
7. Nameplate: ieee C57.12.00 and with "pcb content data (less than 0.1 ppm)"
and "manufacturer's name and type of fluid". 8. Paint base, cabinet and tank
munsell 7GY3.29/1.5 green. The paint coating system shall comply with nema
C57.12.29. 9. Routine and other tests (ieee C57.12.00): cold resistance
measurements, phase relation, ratio, no-load losses and excitation current,
load losses and impedance voltage, dielectric (impulse, applied voltage and
induced voltage) and leak. The following is to be provided along with the
offer: 1. Pcb content certification. 2. Outline drawing of the transformer
with devices indicated. 3. Nameplate data. Estimated shipping via ground to:
Defense Logistics Agency Defense Distribution Center Tracy Depot, Bldg 30, ccp
25600 s. Chrisman Rd. Tracy, ca 95376 The Government intends to make a single
award to the responsible offeror whose offer is the most advantageous to the
Government considering technical acceptability, price, and delivery time. The
following Provisions apply to this acquisition: far 52.212-1 Instructions to
Offerors-Commercial Items (Oct 2000), far 52.212-2 Evaluation-Commercial Items
(Jan 1999, applies with paragraph (a) completed as follows: The Government
will award a contract resulting from this solicitation to the responsible
offeror whose offer conforming to the solicitation will be most advantageous
to the Government, price and other factors considered. The following factors
shall be used to evaluate offers: Technical Acceptability, Price, and Delivery
Time, far 52.212-3 Offeror Representations and Certification Commercial Items
(Jun 2003), far 52.212-4 Contract Terms and Conditions Commercial Items (Feb
2002), far 52.212-5 Contract Terms and Conditions Required to Implement
Statutes or Executive Orders ! Commercial Items (Jun 2003), far 52.232-33
Payment by Electronic Funds Transfer (May 1999), far 52.247-34 f.o.b.
Destination (Nov 1991). Responsible offeror must be active in the Central
Contractor Registration on in accordance with dfars 252.204-7004 (nov 2001).
Duns, tin, and cage Code must be written on submitted quote. Payment shall be
made electronically by dfas Yokota Japan. Full text of
http://farsite.hill.af.mil. The following information must be provided with
this quotation: Commercial and government entity code (Cage). Taxpayer
identification number (Tin). Data universal numbering system (Duns).
Estimated Delivery Date: gsa contract number if applicable Remit to Address
Offers can be faxed to 011816117450959, emailed to william.figueroa@usmc.mil,
or mailed to the Regional Contracting Office, psc 557 box 2000, fpo ap 96379-
2000. Offers must be received no later than 14 Feb 2008, 6:00 pm Eastern
Standard Time. Questions may be addressed to Sgt William Figueroa, by email
at:william.figueroa@usmc.mil.


Company Reports

Get the Dun & Bradstreet Report for Department of the Navy, United States Marine Corps
Company Information
 
Company Name:   Department of the Navy, United States Marine Corps
Address:Login to view contact details
City:Login to view contact details
State/Province:Login to view contact details
Country:Login to view contact details
Zip/Postal Code:Login to view contact details
Phone:Login to view contact details
Fax:Login to view contact details
Contact Person: Login to view contact details
Email:Click here to send this company an email

Didn't find what you were looking for? Post a lead!

Click here to forward this trade lead to a friend!


Worldbid.com Affiliates